| Compatibility | Compatible Indoor Units without DHW Tank | HOP60WIDU | ||
| Compatible Indoor Units with DHW Tank | HOP100/190IDU ; HOP100/190IDU3 | |||
| Heating A7W35 “Air temperature +7°C, 85% RH, water temperature +30/35°C.” | Capacity | kW | 6.2 | |
| Rated Input | kW | 1.24 | ||
| COP | 5 | |||
| Heating A7W45 “Air temperature +7°C, 85% RH, water temperature +40/45°C.” | Capacity | kW | 6.35 | |
| Rated Input | kW | 1.69 | ||
| COP | 3.75 | |||
| Heating A7W55 “Air temperature +7°C, 85% RH, water temperature +47/55°C.” | Capacity | kW | 6 | |
| Rated Input | kW | 2 | ||
| COP | 3 | |||
| Heating A-7W35 “Air temperature -7°C, 85% RH, water temperature +30/35°C.” | Capacity | kW | 6.1 | |
| Rated Input | kW | 2 | ||
| COP | 3.05 | |||
| Cooling A35W18 “Air temperature +35°C, water temperature +23/18°C.” | Capacity | kW | 6.55 | |
| Rated Input | kW | 1.34 | ||
| EER | 4.9 | |||
| Cooling A35W7 “Air temperature +35°C, water temperature +12/7°C.” | Capacity | kW | 7 | |
| Rated Input | kW | 2.33 | ||
| EER | 3 | |||
| Energy Efficiency Class “Defined under moderate climate zone conditions.” | Water Outlet at 35°C | Class | A+++ | |
| Water Outlet at 55°C | Class | A++ | ||
| Seasonal Efficiency | SCOP “Defined under moderate climate zone conditions.” | 35°C | 4.95 | |
| 55°C | 3.52 | |||
| SEER “Defined under moderate climate zone conditions.” | 7°C | 5.37 | ||
| 18°C | 8.21 | |||
| Power Supply | Power Supply | V/Ph/Hz | 220-240/1/50 | |
| Rated Power | W | 2600 | ||
| Rated Current | A | 12 | ||
| Power Cable | mm2 | 3×2,5 | ||
| Automatic Switch | A | C16 | ||
| Refrigerant & Piping | Refrigerant | Type (GWP) | R32 (675) | |
| Quantity in the Device | kg | 1.5 | ||
| Refrigerant Pipes | Liquid Phase | mm (Inch) | 6,35 (1/4”) | |
| Gas Phase | mm (Inch) | 15,88 (5/8”) | ||
| Between the Indoor and Outdoor Units |
Height Difference, Max. | m | 20 | |
| Pipe Lenght, Min. | m | 3 | ||
| Pipe Lenght, Max. | m | 30 | ||
| Additional Refrigerant Charge | Quantity | g/m | 20 | |
| Max. pipe Length without Additional Charge | m | 15 | ||
| Compressor & Fan | Compressor DC Two Rotor Inverter | + | ||
| Fan DC Electric Motor | + | |||
| Sound Levels | Sound Power Level “Tested according to the EN12102-1 standard.” | dB (A) | 58 | |
| Sound Pressure (1 m) | dB (A) | 45 | ||
| Sound Pressure (2 Silent Mode) | dB (A) | 40 | ||
| Dimensions & Weight | Dimension (WxHxD) | mm | 1008×712×426 | |
| Dimension of Package (WxHxD) | mm | 1065×810×485 | ||
| Net / Gross Weight | kg | 58 / 63,5 | ||
| Operation Ambient Temperature Range | Heating | °C | -25 ~ +35 | |
| Cooling | °C | -5 ~ +43 | ||