NIC-NOA 18 - Nordis

NIC-NOA 18

Heating Capacity kW 5,57 (2,37-6,10)
Electricity Consumption kW 1,54 (0,70-1,93)
Power Current A 6,8 (3,1-8,5)
SCOP 4
COP 3.57
Energy efficiency class (moderate climate zone) A+
Cooling Capacity kW 5,28 (2,90-5,59)
Electricity Consumption kW 1,63 (0,72-2,09)
Power Current A 7,2 (3,2-9,2)
SEER 6.3
EER 3.4
Energy efficiency class (moderate climate zone) A++
Power Supply Power Cable mm2 3×1,5
Automatic Switch A 16
Communication Cable mm2 4×1,0
Indoor unit power supply V/Ph/Hz 220-240~/1/50
Outdoor unit power supply V/Ph/Hz 220-240~/1/50
Outdoor Unit Dimension (WxHxD) mm 805x330x554
Dimension of Package (LxWxH) mm 915x370x615
Weight netto kg 32.5
Weight brutto kg 35.2
Air Flow Volume m3/h 2100
Sound Power Level db(A) 63
Cooling Operation Ambient Temperature Range °C -15~50
Heating Operation Ambient Temperature Range °C -20~24
Indoor Unit Dimension (WxHxD) mm 570x570x260
Dimension of Package (LxWxH) mm 662x662x317
Dimension of panel (WxHxD) mm 647x647x50
Dimension of packing dimension (LxWxH) mm 715x715x123
Weight netto kg 16
Weight brutto kg 20.6
Panel weight netto kg 2.5
Panel weight brutto kg 4.5
Air Flow Volume m3/h 720/620/500
Sound Pressure Level db(A) 43/39,5/35,5/29
Connection Pipe Pipe Diameters mm(in) 6,35(1/4)/12,7(1/2)
Refrigerant Charge R32 kg 1.15
GWP 675
Additional amount of Refrigerant g/m 12
Max. Distance Length m 30
Max. Elevation m 20
Other Wi-Fi “Remote control of the NØRDIS four-way cassette NIC-NOA 18 unit requires an additional integrated Wi-Fi module.” -/+