NFW-V500C-2P - Nordis
Model NFW-V500C-2P
Power supply F/V/Hz 220-240/1/50
Air flow (H/M/L) m3/h 862/741/634
CFM 507/435/372
Cooling1 Capacity (H/M/L) kW 4.47/3.98/3.48
Water flow rate (H/M/L) m3/h 0.77/0.68/0.61
Water pressure drop kPa 41.17/33.54/
27.05
Capacity (H/M/L) W 26/18/13
Heating2 Capacity (H/M/L) kW 4.84/4.23/3.62
Water flow rate (H/M/L) m3/h 0.84/0.73/0.64
Water pressure drop kPa 36.82/33.83/
26.26
Capacity (H/M/L) W 22/16/12
Heating3 Capacity (H/M/L) kW 5.68/4.94/4.24
Water flow rate (H/M/L) m3/h 0.77/0.68/0.61
Water pressure drop kPa 43.74/29.69/
23.98
Capacity (H/M/L) W 23/16/12
Sound pressure level (H/M/L) dB(A) 50/46/42
Rated current A 0.32
Fan motor Type DC Motor
Quantity 1
Fan Type Tangential fan
Quantity 1
Coil Row 2
Max. Working pressure MPa 1.6
Diametr mm Φ7
Net dimensions (W×H×D) mm 1072×315×237
Packing size (W×H×D) mm 1180×415×315
Net weight kg 15.1
Gross weight kg 19
Water inlet/outlet pipe col G3/4
Drain pipe mm ODΦ20
Notes: H:High fan speed; M: Medium fan speed;
L: Low fan speed.1 Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/19°C WB,
entering/leaving water temperature 7°C /12°C.2 Heating mode(1): (2-pipe coil): entering air temperature 20°C DB,
entering/leaving water temperature 45/40°C.

3 Heating mode(2): (2-pipe coil): entering air temperature 20°C DB, enter water teperaure/water flow 50°C/*
(same water flow as in standard rating condition in
cooling)