Model | NFD-V1200-4-2P | ||
---|---|---|---|
Power supply | V/Ph/Hz | 220-240/1/50 | |
Air flow (H/M/L) | m3/h | 2134/1617/1119 | |
CFM | 1255/951/658 | ||
Standard external static pressure | Pa | 12Pa (default); 30/50Pa can be set through dial switch on PCB | |
Cooling1 | Capacity (H/M/L) | kW | 9.76/7.81/5.72 |
Water flow rate(H/M/L) | m3/h | 1.78/1.41/1.02 | |
Water pressure drop(H/M/L) | kPa | 22.31/15/8.98 | |
Power input(H/M/L) | W | 109/50/22 | |
Heating2 | Capacity (H/M/L) | kW | 11.76/9.32/6.76 |
Water flow rate(H/M/L) | m3/h | 2.01/1.60/1.15 | |
Water pressure drop(H/M/L) | kPa | 20.04/16.93/9.62 | |
Power input(H/M/L) | W | 119/55/24 | |
Heating3 | Capacity (H/M/L) | kW | 14.34/11.31/8.3 |
Water flow rate(H/M/L) | m3/h | 1.78/1.41/1.02 | |
Water pressure drop(H/M/L) | kPa | 24.94/13.46/13.48 | |
Power input(H/M/L) | W | 121/54/23 | |
Sound pressure level | 0Pa (H/M/L) | dB(A) | 50.7/43.8/34.5 |
Fan motor | Type | DC Motor | |
Quantity | 2 | ||
Fan | Type | Centrifugal, forward-curved blades | |
Quantity | 4 | ||
Coil | Row | 4 | |
Max. working pressure | MPa | 1,6 | |
Diameter | mm | Ø 9.52 | |
Net dimensions (W×H×D) | mm | 1856×241×522 | |
Packing size (W×H×D) | mm | 1905×260×560 | |
Net weight | kg | 41,9 | |
Gross weight | kg | 47,2 | |
Water inlet/outlet pipe | inch | RC3/4 | |
Drain pipe | inch | ZG3/4 |
Notes:
H:High fan speed; M: Medium fan speed; L: Low fan speed.
1: . Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/1 9°C WB, entering/leaving water temperature
7°C /12°C.
2: Heating mode(1): (2-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 45/40°C.3: Heating mode(2): (2-pipe coil): entering air temperature 20°C DB, enter water teperaure/water flow 50°C/*(same
water flow as in standard rating condition in cooling)
4: Sound pressure level is tested in a semi-anechoic test room.
5: The external static pressure test condition is 0 Pa.
H:High fan speed; M: Medium fan speed; L: Low fan speed.
1: . Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/1 9°C WB, entering/leaving water temperature
7°C /12°C.
2: Heating mode(1): (2-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 45/40°C.3: Heating mode(2): (2-pipe coil): entering air temperature 20°C DB, enter water teperaure/water flow 50°C/*(same
water flow as in standard rating condition in cooling)
4: Sound pressure level is tested in a semi-anechoic test room.
5: The external static pressure test condition is 0 Pa.