NFD-V1200-4-2P - Nordis
Model NFD-V1200-4-2P
Power supply V/Ph/Hz 220-240/1/50
Air flow (H/M/L) m3/h 2134/1617/1119
CFM 1255/951/658
Standard external static pressure Pa 12Pa (default); 30/50Pa can be set through dial switch on PCB
Cooling1 Capacity (H/M/L) kW 9.76/7.81/5.72
Water flow rate(H/M/L) m3/h 1.78/1.41/1.02
Water pressure drop(H/M/L) kPa 22.31/15/8.98
Power input(H/M/L) W 109/50/22
Heating2 Capacity (H/M/L) kW 11.76/9.32/6.76
Water flow rate(H/M/L) m3/h 2.01/1.60/1.15
Water pressure drop(H/M/L) kPa 20.04/16.93/9.62
Power input(H/M/L) W 119/55/24
Heating3 Capacity (H/M/L) kW 14.34/11.31/8.3
Water flow rate(H/M/L) m3/h 1.78/1.41/1.02
Water pressure drop(H/M/L) kPa 24.94/13.46/13.48
Power input(H/M/L) W 121/54/23
Sound pressure level 0Pa (H/M/L) dB(A) 50.7/43.8/34.5
Fan motor Type DC Motor
Quantity 2
Fan Type Centrifugal, forward-curved blades
Quantity 4
Coil Row 4
Max. working pressure MPa 1,6
Diameter mm Ø 9.52
Net dimensions (W×H×D) mm 1856×241×522
Packing size (W×H×D) mm 1905×260×560
Net weight kg 41,9
Gross weight kg 47,2
Water inlet/outlet pipe inch RC3/4
Drain pipe inch ZG3/4
Notes:
H:High fan speed; M: Medium fan speed; L: Low fan speed.
1: . Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/1 9°C WB, entering/leaving water temperature
7°C /12°C.
2: Heating mode(1): (2-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 45/40°C.3: Heating mode(2): (2-pipe coil): entering air temperature 20°C DB, enter water teperaure/water flow 50°C/*(same
water flow as in standard rating condition in cooling)
4: Sound pressure level is tested in a semi-anechoic test room.
5: The external static pressure test condition is 0 Pa.