Model | NFD-V200-4-2P | ||
---|---|---|---|
Power supply | F/V/Hz | 220-240/1/50 | |
Air flow (H/M/L) | m3/h | 441/297/227 | |
CFM | 259/174/133 | ||
Standard external static pressure | Pa | 12Pa (default); 30/50Pa can be set through dial switch on PCB | |
Cooling 1 | Capacity (H/M/L) | kW | 2.22/1.59/1.2 |
Water flow rate (H/M/L) | m3/h | 0.40/0.30/0.23 | |
Water pressure | kPa | 2.44/1.52/1 | |
Power input (H/M/L) | W | 17-9-6 | |
Heating 2 | Capacity (H/M/L) | kW | 2.81/2/1.54 |
Water flow rate (H/M/L) | m3/h | 0.51/0.37/0.29 | |
Water pressure | kPa | 2/1.76/1.2 | |
Power input (H/M/L) | W | 18-9-6 | |
Heating 3 | Capacity (H/M/L) | kW | 3.23/2.32/1.75 |
Water flow rate (H/M/L) | m3/h | 0.40/0.30/0.23 | |
Water pressure | kPa | 2.99/1.2/0.71 | |
Power input (H/M/L) | W | 19-9-6 | |
Sound pressure level (H/M/L) | dB(A) | 37.3/27.4/22.2 | |
Fan motor | Type | DC Motor | |
Quantity | 1 | ||
Fan | Type | Centrifugal, forward-curved Blades | |
Quantity | 1 | ||
Coil | Row | 4 | |
Max. Working pressure | MPa | 1.6 | |
Diameter | mm | Φ9.52 | |
Net dimensions (W×H×D) | mm | 741×241×522 | |
Packing size (W×H×D) | mm | 790×260×555 | |
Net weight | kg | 17.8 | |
Gross weight | kg | 20.4 | |
Water inlet/outlet pipe | col | RC3/4 | |
Pipe connections | col | ZG3/4 |
Notes:
H:High fan speed; M: Medium fan speed; L: Low fan speed.
1: Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/1 9°C WB, entering/leaving water temperature 7°C /12°C.
2: Heating mode(1): (2-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 45/40°C.
3: Heating mode(2): (2-pipe coil): entering air temperature 20°C DB, enter water teperaure/water flow 50°C/*(same water flow as in standard rating condition in cooling)
4: Sound pressure level is tested in a semi-anechoic test room.
H:High fan speed; M: Medium fan speed; L: Low fan speed.
1: Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/1 9°C WB, entering/leaving water temperature 7°C /12°C.
2: Heating mode(1): (2-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 45/40°C.
3: Heating mode(2): (2-pipe coil): entering air temperature 20°C DB, enter water teperaure/water flow 50°C/*(same water flow as in standard rating condition in cooling)
4: Sound pressure level is tested in a semi-anechoic test room.